A coordinated protection scheme for DC faults in multi-terminal MMC-HVDC transmission system

机译:多端子MMC-HVDC输电系统直流故障的协调保护方案

获取原文
获取原文并翻译 | 示例

摘要

When a pole-to-pole dc fault occurs, it is desirable that the stations continue contributing to power transfer, rather than blocking. Thus, the current limiting module is connected in series with each arm branch to reduce the large current before the faulty lines are totally isolated by DC circuit breakers. The pole-to-pole fault requires fast identification to trigger the current limiting module. Additionally, the pole-to-ground dc fault with high resistance is another concern. Based on the significant voltage drop on the boundary device of inductance caused by the current surge on the faulty pole, the voltage fault components of both positive pole and negative pole are utilized to conduct a novel protection scheme. The coordinated protection scheme for DC line faults in multi-terminal MMC-HVDC transmission system is presented and simulations based on PSCAD/EMTDC software confirm its effectiveness.
机译:当发生极间直流故障时,希望这些站继续促进功率传输,而不是阻塞。因此,限流模块与每个臂支路串联连接,以在故障线路完全被直流断路器隔离之前减小大电流。极间故障需要快速识别才能触发限流模块。另外,具有高电阻的极对地直流故障是另一个问题。基于故障极上的电流浪涌引起的电感边界器件上的明显压降,利用正极和负极的电压故障分量进行新颖的保护。提出了多端子MMC-HVDC输电系统直流线路故障的协调保护方案,并基于PSCAD / EMTDC软件进行了仿真验证。