首页> 外文期刊>Renewable Power Generation, IET >Ultra-high-speed non-unit non-differential protection scheme for buses of MMC-HVDC grids
【24h】

Ultra-high-speed non-unit non-differential protection scheme for buses of MMC-HVDC grids

机译:用于MMC-HVDC网格总线的超高速非单元非差分保护方案

获取原文
获取原文并翻译 | 示例
       

摘要

Half-bridge modular multilevel converter-based high-voltage direct-current (MMC-HVDC) grids are technically and economically viable solutions to transmit bulk electrical energy generated from geographically dispersed and remote renewable resources. However, due to the half-bridge converter's inability to control fault currents, these grids need specialised protection schemes to increase reliability and equipment safety. This study proposes a non-unit non-differential protection scheme founded on a comparative orientation measure of fault components for buses of half-bridge MMC-HVDC grids. Considering the selected protection strategy, the protection zone of this scheme can also cover a part of the converter station's ac side; in which severe short-circuit faults should be quickly detected and isolated as well since they may cause the entire grid outage. This scheme can be used as the main protection or a backup of the conventional differential current protection, and subsequently, increase the protection system dependability by increasing the functional diversity. The test results disclose that the proposed scheme has superior sensitivity to identify single-pole and double-pole faults with resistances up to 1500 and 2000 omega, respectively, at the protected dc bus with the maximum delay of 1 ms, while it is robust against all ac and dc faults outside the designated protection zone.
机译:基于半桥模块化多电平转换器的高压直流(MMC-HVDC)网格在技术上和经济上可行的解决方案,以传递从地理上分散和远程可再生资源产生的散装电能。然而,由于半桥转换器无法控制故障电流,这些网格需要专门的保护方案来提高可靠性和设备安全性。本研究提出了一种非单位非差分保护方案,其基于半桥MMC-HVDC网格总线的故障组件的比较方向测量。考虑到所选保护策略,该方案的保护区还可以覆盖转换器站的AC侧的一部分;在这种情况下,应快速检测到严重的短路故障,并且均可能导致整个网格中断。该方案可用作传统差分电流保护的主保护或备用,随后,通过提高功能分集来提高保护系统可靠性。测试结果揭示了所提出的方案具有优异的灵敏度,可以分别在受保护的直流总线上识别高达1500和2000欧米加的单极和双极断层,其最大延迟为1毫秒,而它是坚固的指定保护区外的所有AC和DC故障。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号