首页> 外文期刊>IEEE Transactions on Dielectrics and Electrical Insulation >The use of power frequency current transformers as partial discharge sensors for underground cables
【24h】

The use of power frequency current transformers as partial discharge sensors for underground cables

机译:工频电流互感器用作地下电缆的局部放电传感器

获取原文
获取原文并翻译 | 示例
           

摘要

Partial discharge (PD) diagnostics can be used to diagnose insulation defects in medium voltage cables and thereby inform required maintenance planning to extend the lifespan of ageing assets. High frequency current transformers (HFCT) installed on the earth strap at the cable termination are widely used to detect the fast varying pulses resulting from PD. Due to constructional reasons earth strap accessibility in underground cables is often limited. Furthermore in three core cables, phase angle dependency of pulses resulting from PD sometimes fails to induce pulses in the earth screen. This paper investigates an alternative method of PD detection using conventional power frequency current transformers (PFCT) principally used for protection and measurement purposes. This investigation assesses the feasibility of this approach by conducting a magnetic study of the transformer core, frequency response analysis (FRA), and finally capturing and analyzing onsite PD measurements using conventional PFCTs and the developed PD data acquisition/interpretation system. Based on the laboratory and on-site measurement results, PFCTs can be considered for detecting PD. This approach does not require retrofitting additional PD sensors and can also be applied to older switchgear design without any outage. Hence this approach can be considered as a low cost and noninvasive method of PD detection in cables.
机译:局部放电(PD)诊断可用于诊断中压电缆的绝缘缺陷,从而告知所需的维护计划,以延长老化资产的使用寿命。高频电流互感器(HFCT)安装在电缆终端的接地带上,被广泛用于检测由PD引起的快速变化的脉冲。由于结构原因,地下电缆的接地带可及性通常受到限制。此外,在三芯电缆中,PD产生的脉冲的相位角依赖性有时无法在接地屏蔽中感应出脉冲。本文研究了一种使用传统的工频电流互感器(PFCT)进行PD检测的替代方法,该方法主要用于保护和测量目的。这项研究通过对变压器铁心进行磁研究,频率响应分析(FRA),最后使用常规PFCT和已开发的PD数据采集/解释系统来捕获和分析现场PD测量,从而评估了这种方法的可行性。根据实验室和现场测量结果,可以考虑使用PFCT检测PD。这种方法不需要改装额外的PD传感器,也可以在不中断的情况下应用于较旧的开关柜设计。因此,该方法可被视为电缆中PD的低成本,无创检测方法。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号