首页> 外文期刊>E3S Web of Conferences >Study on SO 3 emission test of typical ultra-low emission coal-fired units in western region of Inner Mongolia
【24h】

Study on SO 3 emission test of typical ultra-low emission coal-fired units in western region of Inner Mongolia

机译:中部蒙古西部典型超低排放燃煤装置的 3 排放试验研究

获取原文
           

摘要

To study the effect of types of boilers, pollutant treatment facilities and coal quality on SO_(3), emission concentration of SO_(3)was tested by controlled condensation method for seven typical ultra-low emissions coal-fired units in western region of Inner Mongolia. The test results showed that the SO_(3)emission concentration of all units ranged from 0.36 mg/m~(3)to 2.04 mg/m~(3), much lower than 5 mg/m~(3), so there was no need to add SO_(3)removal facilities. For the units burning the coal of same sulfur content, which adopt LLTESP and WESP has the lower SO_(3)emission concentration. The SO_(3)emission concentration can also be controlled at a lower value when SNCR and double-tower double-cycle WFGD technology are adopted in the unit burning medium-high sulfur coal.
机译:为研究锅炉类型,污染物治疗设施和煤炭质量的效果(3),通过对内部西部地区的七种典型超低排放燃煤装置进行控制的冷凝法测试SO_(3)的排放浓度 蒙古。 测试结果表明,所有单位的SO_(3)排放浓度范围为0.36mg / m〜(3)至2.04mg / m〜(3),远低于5mg / m〜(3),所以有 无需添加SO_(3)删除设施。 对于燃烧相同硫含量的煤炭的单位,采用LLTESP和WESS具有较低的SO_(3)发射浓度。 当在燃烧的中高硫煤中采用SNCR和双塔双循环WFGD技术时,也可以以较低的值控制SO_(3)发射浓度。