首页> 外文期刊>E3S Web of Conferences >Comparison of Grounding Grid Parameters Between Copper and Galvanized Flat Steel
【24h】

Comparison of Grounding Grid Parameters Between Copper and Galvanized Flat Steel

机译:铜镀锌扁钢接地网格参数比较

获取原文
获取外文期刊封面目录资料

摘要

In the intelligent substation, the shell of the secondary equipment is connected to the ground grid locally. When the short circuit fault current is injected into the grounding grid to cause the ground potential rise, the potential difference between the two points of the grounding grid will affect the normal operation of the secondary equipment. In this paper, aiming at the grounding grid of a 220kV substation, the grounding impedance, ground potential rise and ground potential difference between galvanized flat steel and copper grounding grid are calculated by using CDEGS software. The results show that the copper ground grid has a significant effect on reducing the potential difference of the ground grid.
机译:在智能变电站中,二级设备的壳体在本地连接到地面网格。 当短路故障电流注入接地网格以导致地电位上升时,接地网格的两个点之间的电位差会影响二级设备的正常操作。 本文通过使用CDEGS软件计算镀锌扁钢和铜接地网之间的接地电视,接地阻抗,接地电位上升和地电位差。 结果表明,铜接地电网对降低地面栅格的电位差具有显着影响。