首页> 外文期刊>MATEC Web of Conferences >The Effect of Refrigerant Charge on the Performance of a Split-Unit Type Air Conditioner Using R22 Refrigerant
【24h】

The Effect of Refrigerant Charge on the Performance of a Split-Unit Type Air Conditioner Using R22 Refrigerant

机译:制冷剂充电对使用R22制冷剂的分裂单元型空调性能的影响

获取原文
           

摘要

Numerous air conditioners are running without a proper refrigerant charge due to leakage and improper charging during installation. Therefore, there is a need to understand the performance of the air conditioner if it is not properly charged for the means of optimal operation and cost saving. This study is focusing on the usage of a used small capacity split-unit type air conditioner using R-22 refrigerant. The objective is to study the condenser performance over a variation of refrigerant charges. From the results, it is clear that the optimum refrigerant charge is 100%. The highest cooling capacity and COP were 3,330 J/s and 3.05 respectively.
机译:许多空调在安装期间由于泄漏和充电而没有适当的制冷剂电荷而运行。因此,如果没有正确充电,需要了解空调的性能,以获得最佳操作和成本节省的装置。本研究专注于使用R-22制冷剂的使用小容量分体单元型空调的使用。目的是在制冷剂电荷的变化上研究冷凝器性能。从结果中,很明显,最佳制冷剂充电是100%。最高的冷却能力和COP分别为3,330 j / s和3.05。