Global Harmonic Rate Assessment in the Electricity Distribution Network in Niamey City: Case Studies of Domestic, Industrial and Hospital Substations

机译:尼亚美城电力分配网络的全球谐波率评估:国内,工业和医院变电站的案例研究

获取原文
   

获取外文期刊封面封底 >>

       

摘要

Like others countries of the world, in Niger also, we are witnessing an increasing use of non-linear electric loads in the domestic, hospital and industrial sectors. However, these loads degrade the shape of the electrical signal and cause disastrous effects to the equipment of the distribution system and the devices which are connected to the network. This article highlights the presence of electric harmonics in the distribution network in Niamey city. In order to do this, measurements were taken at the secondary level of the substations using an energy quality analyze style="white-space:nowrap;">r (FLUKE 1735). By using this measuring instrument, we quantified the voltage and current Total Harmonic Distortion (THD) in the three substations. The results obtained show that, although the statutable rates set by the standards are not exceeded for phase conductors, the neutral contains a very critical percentage of distortion on the residential and hospital substations. Moreover, this assessment made it possible to observe the variation of harmonics in the presence of voltage drops.
机译:与世界其他国家一样,在尼日尔也,我们目睹了国内,医院和工业部门的非​​线性电荷越来越多地利用。然而,这些负载降低了电信号的形状并对配送系统的设备和连接到网络的设备引起灾难性影响。本文突出了尼蒙城配电网中的电力谐波存在。为了做到这一点,使用能量质量分析<跨度=“白色空间:nowrap;”> R (FLUKE 1735),在变电站的二级水平上进行测量。 。通过使用该测量仪器,我们在三个变电站中量化了电压和电流总谐波失真(THD)。获得的结果表明,尽管不超过标准设定的定期率不超过相导体,但中性含有在住宅和医院变电站上的扭曲百分比非常关键。此外,该评估使得可以在电压下降中观察谐波的变化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号