Global Harmonic Rate Assessment in the Electricity Distribution Network in Niamey City: Case Studies of Domestic, Industrial and Hospital Substations

机译:尼亚美市配电网中的全球谐波费率评估:家庭,工业和医院变电站的案例研究

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Like others countries of the world, in Niger also, we are witnessing an increasing use of non-linear electric loads in the domestic, hospital and industrial sectors. However, these loads degrade the shape of the electrical signal and cause disastrous effects to the equipment of the distribution system and the devices which are connected to the network. This article highlights the presence of electric harmonics in the distribution network in Niamey city. In order to do this, measurements were taken at the secondary level of the substations using an energy quality analyze r (FLUKE 1735). By using this measuring instrument, we quantified the voltage and current Total Harmonic Distortion (THD) in the three substations. The results obtained show that, although the statutable rates set by the standards are not exceeded for phase conductors, the neutral contains a very critical percentage of distortion on the residential and hospital substations. Moreover, this assessment made it possible to observe the variation of harmonics in the presence of voltage drops.
机译:像世界其他国家一样,在尼日尔,我们也目睹了家用,医院和工业部门越来越多地使用非线性电力负载。但是,这些负载会降低电信号的形状,并对配电系统的设备和连接到网络的设备造成灾难性的影响。本文重点介绍了尼亚美市配电网络中谐波的存在。为此,使用电能质量分析仪(FLUKE 1735)在变电站的二级进行测量。通过使用该测量仪器,我们对三个变电站中的电压和电流总谐波失真(THD)进行了量化。所获得的结果表明,尽管不超过标准规定的相导体的可计算比率,但中性点在住宅和医院变电站中的畸变百分比却非常关键。而且,该评估使得可以观察到存在电压降时谐波的变化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号