首页> 外文期刊>IFAC PapersOnLine >Research on Fault Detection Method for Air Handling Units System
【24h】

Research on Fault Detection Method for Air Handling Units System

机译:空气处理机组系统故障检测方法研究

获取原文
           

摘要

Heating, ventilation, and air conditioning (HVAC) system is an important system in the building. If the HVAC system can run in a fault-free condition, energy consumption will be reduced directly. In HVAC system, the air handling units systems (AHUs) are used to deal with the heat change between outdoor environment and the building, which is a key subsystem of the HVAC system. If the AHUs run under a fault condition, energy consumption will be increased. In fault detection, the state of AHUs will be affected by outdoor environment. The influence from outdoor may mislead the alarm of fault detection and reduce the precision of detecting. By dynamically monitoring the fluctuation of AHUs parameters, we can get the state of AHUs in time, and there will be an alarm song if the fault occurs. This paper introduces a fault detection method to provide a new perspective for AHUs fault detection. Through this method, we obtain the states of the AHUs through unscented Kalman filter, and set the dynamic-control limit by Statistical Process Control (SPC) method to get alarm of fault condition. The method can get system’s states accurately, and the false alarm will be well controlled.
机译:暖气,通风和空调(HVAC)系统是建筑物中的重要系统。如果HVAC系统可以在无故障的情况下运行,则将直接降低能耗。在HVAC系统中,空气处理单元系统(AHU)用于处理室外环境与建筑物之间的热变化,这是HVAC系统的关键子系统。如果AHU在故障条件下运行,则会增加能耗。在故障检测中,AHU的状态会受到室外环境的影响。室外的影响可能会误导故障检测报警,降低检测精度。通过动态监控AHU的参数波动,可以及时了解AHU的状态,如果出现故障会发出警报声。本文介绍了一种故障检测方法,为AHU的故障检测提供了新的视角。通过这种方法,我们通过无味卡尔曼滤波器获得了AHU的状态,并通过统计过程控制(SPC)方法设置了动态控制极限,以得到故障状态的警报。该方法可以准确地获取系统状态,并且可以很好地控制错误警报。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号