首页> 外文期刊>Journal of Thermodynamics >Analysis of a New Dissipation System for a Solar Cooling Installation
【24h】

Analysis of a New Dissipation System for a Solar Cooling Installation

机译:新型太阳能散热装置的耗散系统分析

获取原文
   

获取外文期刊封面封底 >>

       

摘要

This paper describes a solar absorption cooling installation located at the University of Zaragoza (Spain). The installation is based on the performance of an absorption chiller. The solar cooling system consists of 37,5 m2of flat plate collector, a 4.5 kW, single-effect LiBr-H2O absorption chiller, and a dry cooling tower. The installation provides cooling to a gymnasium belonging to the sports center of the university. To carry out the installation analysis, the system was continuously monitored. In 2007, 2008 and 2009, several studies have been performed in order to analyze the full system operation. The measured data showed the strong influence of the cooling water temperature and the generator driving temperature on the COP. Due to the experimental evidence of the influence of the cooling water temperature, a new heat rejection system based on a geothermal heat sink has been installed and studied.
机译:本文介绍了位于西班牙萨拉戈萨大学的太阳能吸收式冷却装置。安装基于吸收式制冷机的性能。太阳能冷却系统由37.5平方米的平板集热器,4.5千瓦,单效LiBr-H2O吸收式制冷机和干式冷却塔组成。该设备为属于大学运动中心的体育馆提供冷却。为了进行安装分析,对系统进行了持续监控。在2007年,2008年和2009年,已经进行了几项研究,以分析整个系统的运行情况。实测数据表明冷却水温度和发电机驱动温度对COP的影响很大。由于冷却水温度影响的实验证据,已经安装并研究了一种基于地热散热器的新型散热系统。