首页> 外文期刊>Journal of Thermal Science and Technology >Performance Analysis of Frostless Heat Exchanger by Spreading Antifreeze Solution on Heat Exchanger Surface
【24h】

Performance Analysis of Frostless Heat Exchanger by Spreading Antifreeze Solution on Heat Exchanger Surface

机译:通过在换热器表面散布防冻液的无霜换热器性能分析

获取原文
       

摘要

The effect of antifreeze solution liquid film on the frost prevention is experimentally investigated. It is desirable that the antifreeze solution spreads widely on the heat exchanger surface forming thin liquid film to prevent frost nucleation while having small thermal resistance across the film. A porous layer coating technique is adopted to improve the wettability of the antifreeze solution on heat exchanger surface. The antifreeze solution spreads widely on the heat exchanger surface with 100 μm thickness by the capillary force resulted from the porous structure. It is observed that the antifreeze solution liquid film prevents a heat exchanger from frosting. The reductions of heat and mass transfer rate caused by the thin liquid film are only 1-2% compared with those for non-liquid film surface.
机译:实验研究了防冻液液膜对防霜的作用。理想的是,防冻剂溶液在热交换器表面上广泛散布,形成薄的液膜,以防止霜冻成核,同时在整个膜上具有小的热阻。采用多孔层涂覆技术以提高防冻剂溶液在热交换器表面上的润湿性。通过多孔结构产生的毛细作用力,防冻剂溶液以100μm的厚度广泛分布在热交换器表面。观察到防冻溶液液膜防止热交换器结霜。与非液膜表面相比,由液膜引起的传热和传质速率的降低仅为1-2%。