The Method for Measuring the Loop Resistance and the Temperature Rise Calculation of GIS Conductor Pole

机译:GIS导体极的回路电阻测量方法和温升计算

获取原文
           

摘要

This paper studies the method for measuring the loop resistance of GIS conductor pole based on the super capacitor producing impulse current up to several thousand amperes. This method overcomes the limitations of conventional diagnostic method. Typical GIS conductor poles are chosen. Based on FEA and lab tests, the effect of different forms of current and contact condition, relationship between the temperature of contact and the loop resistance is researched. In full- scale testing under realistic operating conditions on the new 220 kV GIS using prototype instrumentation a very good sensitivity in an early stage was obtained.
机译:本文研究了基于超级电容器产生高达几千安培的冲击电流的GIS导体极的环路电阻的测量方法。该方法克服了常规诊断方法的局限性。选择典型的GIS导体极。基于有限元分析和实验室测试,研究了不同形式的电流和接触条件的影响,以及接触温度和回路电阻之间的关系。使用原型仪器在新的220 kV GIS上的实际操作条件下进行全面测试,可以在早期获得非常好的灵敏度。