首页> 外文期刊>Journal of Physics: Conference Series >Modelling and resonance analysis of wind power integration via flexible HVDC considering wind speed and wind farm location
【24h】

Modelling and resonance analysis of wind power integration via flexible HVDC considering wind speed and wind farm location

机译:考虑风速和风电场位置的通过柔性高压直流输电进行风电集成的建模和共振分析

获取原文
       

摘要

Field experience has shown that harmonic resonance may occur in wind farms integration through a flexible HVDC transmission system. The impact on resonance characteristics from wind speed and length of the connection line from wind farm to flexible HVDC converter station is studied in this paper. First, the system model of wind farm integration through flexible HVDC system is established, including the whole structure of electrical model, control structures of converters and the impedance measurement model. Then, the effect of the line length and wind speed on the impedance characteristics of interconnected system is analyzed, and the aggregated RLC circuit approach is used to evaluate the risk of potential resonance quantitatively. Finally, the simulation results on the RT-LAB platform validate the theoretical analysis.
机译:现场经验表明,通过灵活的HVDC传输系统,风电场集成中可能会发生谐波谐振。研究了风速和风电场到柔性HVDC换流站的连接线长度对谐振特性的影响。首先建立了通过柔性高压直流输电系统进行风电场集成的系统模型,包括电气模型的整体结构,变流器的控制结构和阻抗测量模型。然后,分析了线长和风速对互连系统阻抗特性的影响,并使用聚合的RLC电路方法定量评估潜在共振的风险。最后,在RT-LAB平台上的仿真结果验证了理论分析。