首页> 外文期刊>Journal of Electromagnetic Analysis and Applications >Investigation of Power Factor Behavior in AC Railway System Based on Special Traction Transformers
【24h】

Investigation of Power Factor Behavior in AC Railway System Based on Special Traction Transformers

机译:基于特殊牵引变压器的交流铁路系统功率因数特性研究

获取原文
       

摘要

The single-phase traction load has essentially an unbalance characteristic at the Point of Common Coupling (PCC), which injects harmonic into the utility grid. In this paper, the effect of harmonic distortion and unbalance loading are investigated simultaneously for electrical railway systems. Special traction transformers (i.e. single-phase, V/V, Wye-Delta, Scott, and Le Blanc) are used between the utility grid and the traction load. For analysis, different defini-tions of power factors are considered, which are presented by IEEE Std.1459. The detailed simulation study is made with MATLAB/SIMULINK program to represent the impacts of harmonic components and unbalance loading on the power factor behavior in the Electrical Railway systems.
机译:单相牵引负载在公共耦合点(PCC)处基本上具有不平衡特性,该特性将谐波注入公用电网。本文同时研究了电力铁路系统的谐波畸变和不平衡载荷的影响。在公用电网和牵引负载之间使用特殊的牵引变压器(即单相,V / V,Wye-Delta,Scott和Le Blanc)。为了进行分析,考虑了功率因数的不同定义,这些定义由IEEE Std.1459提出。使用MATLAB / SIMULINK程序进行了详细的仿真研究,以表示谐波分量和不平衡负载对电气铁路系统中功率因数行为的影响。