Monitoring and diagnosis of power transformer in power systems have been examined and debated significantly in last few decades. Recently, more researchers have expressed their interest in these issues as the utilities and network operators operating under a rising cost-effecting pressure. Especially, in studying to monitor winding faults which is found to be the most common fault within transformers. This paper addresses the issue of the effect of inter-windings short circuit fault in a Dyn11 connected transformer. The specific aim is to study the effect of fault at winding of other phases to the response of measured phase. Frequency Response Analysis (FRA) which is discovered to be a powerful and sensitive method to examine and evaluate the condition, including the mechanical reliability of the transformer windings is used.
机译:在过去的几十年中,对电力系统中电力变压器的监视和诊断进行了广泛的讨论。最近,越来越多的研究人员对这些问题表示了兴趣,因为公用事业和网络运营商正在承受越来越高的成本影响压力。特别是在研究监视绕组故障时,这是变压器内部最常见的故障。本文解决了在Dyn11连接的变压器中绕组间短路故障的影响问题。具体目的是研究其他相绕组的故障对被测相响应的影响。频率响应分析(FRA)是一种用于检查和评估条件(包括变压器绕组的机械可靠性)的强大而灵敏的方法。