摘要

Corona-originated discharge of DC transmission lines is the main reason for the radiated electromagnetic interference (EMI) field in the vicinity of transmission lines. A joint time-frequency analysis technique was proposed to extract the radiated EMI current (excitation current) of DC corona based on corona current statistical measurements. A reduced-scale experimental platform was setup to measure the statistical distributions of current waveform parameters of aluminum conductor steel reinforced. Based on the measured results, the peak value, root-mean-square value and average value with 9 kHz and 200 Hz band-with of 0.5 MHz radiated EMI current were calculated by the technique proposed and validated with conventional excitation function method. Radio interference (RI) was calculated based on the radiated EMI current and a wire-to-plate platform was built for the validity of the RI computation results. The reason for the certain deviation between the computations and measurements was detailed analyzed.
机译:直流传输线的电晕放电是传输线附近辐射电磁干扰(EMI)场的主要原因。提出了一种联合时频分析技术,基于电晕电流统计测量值提取直流电晕的辐射EMI电流(励磁电流)。建立了一个缩小规模的实验平台,以测量铝导体钢增强的电流波形参数的统计分布。根据测量结果,通过提出的技术计算了9 kHz和200 Hz带宽的0.5 MHz辐射EMI电流的峰值,均方根值和平均值,并通过常规激励函数方法进行了验证。基于辐射的EMI电流计算无线电干扰(RI),并建立线对板平台以确保RI计算结果的有效性。详细分析了计算与测量之间存在一定偏差的原因。