Electrolytic corrosion of water pipeline system in the remote distance from stray currents—Case study

机译:远离杂散电流的输水管道系统的电解腐蚀—案例研究

获取原文
       

摘要

Case study of corrosion failure of urban water supply system caused by the harmful effects Received 5 November 2015 of stray currents was presented. The failure occurred at a site distant from the sources of Received in revised form 1 February 2016 Accepted 18 March 2016 Available online 24 March 2016 these currents namely the tramway and railway traction systems. Diagnosis revealed the stray currents flow to pipeline over a remote distance of 800/1000 m from the point of failure. At the point of failure stray currents flowed from the pipeline to the ground through external insulation defects, causing the process of electrolytic corrosion of the metal. Long distance between the affected section of the pipeline and the sources of stray currents excludes the typical protection against stray currents in the form of electrical polarized.
机译:介绍了2015年11月5日收到的杂散电流对城市供水系统的有害影响引起的腐蚀失效的案例研究。故障发生在远离接收方的站点上。接收方以修订版的形式2016年2月1日接受2016年3月18日可用这些电流即电车和铁路牵引系统于2016年3月24日在线可用。诊断发现杂散电流从故障点流向管道的距离为800/1000 m。在故障点,杂散电流通过外部绝缘缺陷从管道流到地面,从而导致金属的电解腐蚀过程。管道的受影响部分与杂散电流源之间的距离过长,无法针对电极化形式的杂散电流进行典型的保护。