Acid conductivity monitoring at demineralization plant: an important performance parameter

机译:脱盐厂的酸电导率监测:重要的性能参数

获取原文
获取原文并翻译 | 示例
       

摘要

The acid conductivity measurement is universally adopted for the monitoring of water-steam cycles as it can detect low level of contaminant on a continuous basis. This paper discusses the monitoring of acid conductivity at the inlet of the demineralization plant for assessing the output of the ion exchangers. An observation of data collected over a period of 14 months shows a strong correlation between output between regeneration (OBR) and acid conductivity. OBR is inversely proportional to acid conductivity with a correlation coefficient of -0.907. A drastic change in acid conductivity was observed when water level of the freshwater reservoir went below a depth of 3.8 m. The present study was undertaken with the intention to develop a simple and rugged method to measure the performance of ion exchangers in service and to find out the root cause of change in water quality after the freshwater reservoir level drops below a certain depth.
机译:由于酸电导率测量可以连续检测到少量污染物,因此普遍用于监测水蒸汽循环。本文讨论了在脱盐工厂入口处对酸电导率的监控,以评估离子交换剂的输出。对14个月期间收集的数据的观察表明,再生(OBR)的输出与酸电导率之间具有很强的相关性。 OBR与酸电导率成反比,相关系数为-0.907。当淡水水库的水位低于3.8 m时,观察到酸电导率发生了巨大变化。进行本研究的目的是开发一种简单而坚固的方法来测量使用中的离子交换剂的性能,并找出在淡水水位降至一定深度以下后水质变化的根本原因。