首页> 外文期刊>Chemical and Petroleum Engineering >EXPERIMENTAL STUDY OF HEAT EXCHANGE AND AERODYNAMIC AND THERMAL CONTACT RESISTANCE OF STAGGERED BUNDLES OF TUBES WITH SPIRAL ROLLED FINS OF AIR-COOLED DEVICES
【24h】

EXPERIMENTAL STUDY OF HEAT EXCHANGE AND AERODYNAMIC AND THERMAL CONTACT RESISTANCE OF STAGGERED BUNDLES OF TUBES WITH SPIRAL ROLLED FINS OF AIR-COOLED DEVICES

机译:螺旋轧制螺旋翅片交错束束束热交换和空气动力和热接触电阻的试验研究

获取原文
获取原文并翻译 | 示例
           

摘要

Results of a study of the thermal and dynamic characteristics of three types of six-row checkerboard bundles in a transverse flow in the interval of Reynolds number Re = (3-18)×10~3 are presented. The experimental data are generalized by similarity equations. The heat-exchange coefficients of each transverse row of the bundle are measured and features that arise in the variation of heat exchange by row of the bundle are identified. The mean value of the thermal contact resistance in the range of variation of the temperature of the contact surfaces 79-95°C is found to be equal to 2.13·10~(-4) m~2· K/W.On the basis of results of the study it is shown that the use of an equilateral configuration of tubes in bundles should be rejected and replaced by an isosceles configuration with steps S_1 = 68-69 mm and S_2 = 55.4 mm, a configuration that is advantageous in terms of energy and on the basis of a cost-benefit analysis.
机译:提出了在雷诺数Re =(3-18)×10〜3的横向流中三种类型的六行棋盘束的热和动态特性的研究结果。实验数据通过相似性方程概括。测量束的每个横行的热交换系数,并识别通过束的行的热交换变化中出现的特征。发现接触表面温度的变化范围内的热接触电阻的平均值等于2.13·10〜(-4)m〜2·k / w.on研究结果表明,在步骤S_1 = 68-69mm和S_2 = 55.4mm的情况下,应拒绝并替换在束中的等边结构的使用,并通过步骤S_1 = 68-69mm,这是一个有利的配置能量和基于成本效益分析。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号