Formaldehyde exposure risk in air-conditioned offices of Hong Kong

机译:香港空调办事处的甲醛暴露风险

获取原文
获取原文并翻译 | 示例
           

摘要

Formaldehyde (HCHO) is a carcinogenic toxicant commonly present in an air-conditioned office environment. This study examines the lifetime exposure risk of HCHO in air-conditioned offices of Hong Kong under various indoor environmental conditions. Using the regional indoor air quality assessment results of 511 Hong Kong offices recorded from 1996 to 2005, together with the mathematical correlations among HCHO exposure concentration, ventilation and thermal environment verified at 43 other local air-conditioned offices, the exposure risk in terms of loss of life expectancy (USEPA standard) was predicted for an office environment preset at certain air temperature and atmospheric carbon dioxide (CO_2) level. It was reported that the average increment of HCHO exposure risk was 2% for every 1℃ increment in the air temperature range of 22.5-25.5℃, or 2.5% for every 10ppm increment in the CO_2 concentration range of 800-1000 ppm. This study presents useful information on HCHO exposure risk evaluation for air-conditioned offices associated with various policies on indoor air temperature and ventilation demands.rnPractical applications: This study outlines an approach to lifetime exposure risk assessment for HCHO inhaled in air-conditioned offices of Hong Kong under various indoor environmental conditions. In a typical office environment, the findings demonstrated that the average increment of HCHO exposure risk was 2% for every 1℃ increment in air temperature or 2.5% for every 10 ppm increment in CO_2 concentration.
机译:甲醛(HCHO)是致癌的有毒物质,通常存在于空调办公室环境中。这项研究研究了在各种室内环境条件下香港空调办公室中HCHO的终生暴露风险。使用1996年至2005年记录的511个香港办事处的区域室内空气质量评估结果,以及在其他43个本地空调办事处验证的HCHO暴露浓度,通风和热环境之间的数学关系,以损失为单位的暴露风险对于在一定气温和大气二氧化碳(CO_2)水平下预设的办公环境,可以预测预期寿命(USEPA标准)。据报道,在22.5-25.5℃的空气温度范围内,每增加1℃,HCHO暴露风险的平均增加量为2%,而在800-1000 ppm的CO_2浓度范围内,每增加10ppm,HCHO暴露风险为2.5%。这项研究为空调办公室的HCHO暴露风险评估提供了有用的信息,并与室内空气温度和通风需求的各种政策相关联。rn实际应用:本研究概述了对香港空调办公室吸入的HCHO进行终生暴露风险评估的方法在各种室内环境条件下使用。在典型的办公环境中,研究结果表明,空气温度每升高1℃,HCHO暴露风险的平均增加量为2%,而CO_2浓度每增加10 ppm则增加2.5%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号