An experimental investigation of the performance of natural, mechanical and hybrid ventilation systems was carried out in an urban measurement campaign during summer period 2002 in Athens, Greece. Three building apartments characterized by different geometry and located in two street canyons with different orientation were studied. The aim was to show the impact of the urban environment on the ventilation efficiency of natural and hybrid systems. The tracer gas decay method has been applied during the experimental procedures with one (N_2O) and two tracer gases (N_2O and SF_6). Based on the results of air-exchange rates using multizone methods from a previous study, a further analysis is performed in the present work for the evaluation of the performance of different ventilation systems in urban conditions, with emphasis on the ventilation efficiency. A methodology to estimate the air-exchange efficiency, on the basis of room mean age of air, in multitracer gas experiments is introduced. In spite of the reduced wind speeds due to the canyon effect, appreciable ventilation rates can be obtained with natural ventilation, especially when cross-ventilation with two or more windows is measured. For single-sided ventilation or under calm conditions, hybrid ventilation has only a slight advantage over natural, either in terms of air-exchange rates or of air-exchange efficiencies.
机译:在2002年夏季的希腊城市测量活动中,对自然,机械和混合通风系统的性能进行了实验研究。研究了三个具有不同几何形状并位于两个方向不同的街道峡谷中的建筑公寓。目的是展示城市环境对自然和混合系统通风效率的影响。示踪气体衰减法已在实验过程中应用于一种(N_2O)和两种示踪气体(N_2O和SF_6)。基于以前研究中使用多区域方法的空气交换率结果,本工作进行了进一步分析,以评估城市条件下不同通风系统的性能,重点是通风效率。介绍了一种在多示踪气体实验中根据室内平均年龄估算空气交换效率的方法。尽管由于峡谷效应而导致风速降低,但自然通风仍可获得可观的通风率,尤其是在测量到两个或多个窗户的交叉通风时。对于单侧通风或在安静条件下,混合通风在空气交换率或空气交换效率方面仅比自然通风略有优势。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号