首页> 外文期刊>Building and Environment >In-situ implementation and validation of a CXVbased adaptive demand-controlled ventilation strategy in a multi-zone office building
【24h】

In-situ implementation and validation of a CXVbased adaptive demand-controlled ventilation strategy in a multi-zone office building

机译:多区域办公楼中基于CXV的自适应需求控制通风策略的现场实施和验证

获取原文
获取原文并翻译 | 示例
       

摘要

This paper presents the in-situ implementation and validation of a CO_2-based adaptive demand-controlled ventilation (DCV) strategy in a super high-rise building in Hong Kong. The adaptive DCV strategy employs a dynamic multi-zone ventilation equation for multi-zone air-conditioning systems, in which a CO_2-based dynamic occupancy detection scheme is used for online occupancy detection. This strategy is implemented in an independent Intelligent Building Management and Integration platform (IBmanager), which communicates with the main station of the Building Management System (BMS) through a communication protocol and interface. The performance of this DCV strategy is practically tested and validated by comparing with that of the original fixed outdoor air flow rate control strategy used in site. The implementation architecture and test results including energy and environmental performances represented. Since the accuracy and reliability of the major measurement instrumenta-tions affect the actual performance of the DCV strategy significantly, the commissioning and calibration of major measurement instrumentations are presented as well.
机译:本文介绍了在香港的超高层建筑中基于CO_2的自适应需求控制通风(DCV)策略的现场实施和验证。自适应DCV策略为多区域空调系统采用了动态多区域通风方程,其中基于CO_2的动态居住检测方案用于在线居住检测。该策略在独立的智能建筑管理和集成平台(IBmanager)中实现,该平台通过通信协议和接口与建筑管理系统(BMS)的主站进行通信。通过与现场使用的原始固定室外空气流量控制策略进行比较,对该DCV策略的性能进行了实际测试和验证。实施架构和测试结果包括能源和环境绩效。由于主要测量仪器的准确性和可靠性会严重影响DCV策略的实际性能,因此还介绍了主要测量仪器的调试和校准。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号