Variation of clean air delivery rate and effective air cleaning ratio of room air cleaning devices

机译:室内空气清洁装置的清洁空气输送率和有效空气清洁率的变化

获取原文
获取原文并翻译 | 示例
           

摘要

Air cleaners have been normally used to remove airborne particles from indoor air, and these devices are normally rated according to their clean air delivery rate (CADR), which is a measure of the delivery of contaminant-free air. This study evaluated and compared the performance of room air cleaning devices in removing submicron-sized particles. Most of the CADRs that were experimentally obtained were lower than that stated by the manufacturer. The difference between the experimental measurements and the device specifications gradually increases as the CADR increased. For the same air cleaning device, the experimental CADR decreased as the size of the test chamber increased. The effective air cleaning ratio (EACR) was newly defined to provide an accurate measure of the CADR. The EACR is the ratio of the real CADR to the stated CADR. The experiments and simulations revealed that the EACR of the air cleaning devices was in the range of 0.70-0.83. The ECAR is little changed with respect to the size of the test chamber and the flow rate of the air cleaning devices, unlike the experimental CADR. The real CADR is affected by the filtration efficiency, the flow rate, and the design of the air cleaning device as well as the size of the test particles. The real CADR decreases as the particle size increases. Therefore, the recommended CADR of air cleaning devices for use in facilities with sensitive populations or hospitals must be higher than that for general purpose use.
机译:空气滤清器通常用于从室内空气中清除空气中的颗粒物,这些设备通常根据其清洁空气输送率(CADR)进行评级,这是对无污染空气输送的一种度量。这项研究评估并比较了室内空气净化装置在去除亚微米级颗粒上的性能。通过实验获得的大多数CADR均低于制造商规定的CADR。随着CADR的增加,实验测量值与设备规格之间的差异逐渐增大。对于相同的空气净化设备,实验CADR随测试室尺寸的增加而减小。新定义了有效空气清洁比(EACR),以提供CADR的准确测量。 EACR是实际CADR与指定CADR之比。实验和模拟表明,空气净化装置的EACR在0.70-0.83的范围内。与实验CADR不同,ECAR在测试室的尺寸和空气净化装置的流量方面几乎没有变化。实际的CADR受过滤效率,流速,空气净化装置的设计以及测试颗粒尺寸的影响。实际CADR随着粒径的增加而降低。因此,建议在人口敏感或医院设施中使用的空气净化器的CADR必须高于一般用途。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号