Under-floor Pressure Control: A Superior Method of Controlling Data Center Cooling

机译:地板下压力控制:一种控制数据中心冷却的高级方法

获取原文
获取原文并翻译 | 示例
           

摘要

Analytical evidence and experimental results suggest that return air temperature control limits the effectiveness and efficiency of data center cooling. Return air temperature control rarely, and often only coincidentally, enables a close match of air provisioning relative to IT equipment consumption. Other methods that divorce the flow control from the temperature control offer much better opportunities to tune cooling performance, either manually or automatically, producing improvements in operational energy and capital usage. Under-floor static pressure control is one such method. This paper presents evidence that suggests that static pressure control is a viable and often superior alternative to return air temperature control.
机译:分析证据和实验结果表明,回风温度控制限制了数据中心冷却的有效性和效率。回风温度控制很少,而且通常只是同时发生,可以使空气供应相对于IT设备消耗紧密匹配。将流量控制与温度控制分开的其他方法为手动或自动调节冷却性能提供了更好的机会,从而改善了操作能量和资本使用。地板下静压控制就是这样一种方法。本文提供的证据表明,静压控制是回风温度控制的可行且通常更好的选择。