In this study, the effects of critical operational constraints on the operational domain of a double-effect lithium bromide/water absorption refrigeration system and its performance were investigated. These constraints were determined as the equivalence state of concentrations, the thermal unbalance between the system components of high-pressure condenser and low-pressure generator, freezing and crystallization risk of lithium bromide/water solution. For the system analysis, a simulation program was developed, and its detailed solution procedure was presented. The program outputs were initially validated with the literature. Subsequently, parametric studies were conducted for broad ranges of the component temperatures. The results demonstrate that the considered constraints were essential for acceptable design and the operational control of double-effect absorption refrigeration systems. The simulations will help to figure out under which operating conditions a double-effect absorption refrigeration system functions effectively and what kind of control strategies are essentially required to increase the coefficient of performance. Based on the operation scenario of fixed high-pressure generator temperature, the proposed system can enhance the coefficient of performance up to 31% and 84% as compared to its counterparts which function under the variable high-pressure generator temperature and the pinch point temperature difference (5K between the high-pressure condenser and the low-pressure generator), respectively.
机译:在这项研究中,研究了关键操作约束对双效溴化锂/吸水制冷系统的操作范围及其性能的影响。这些约束条件被确定为浓度的等效状态,高压冷凝器和低压发生器的系统组件之间的热不平衡,溴化锂/水溶液的冻结和结晶风险。为了进行系统分析,开发了一个仿真程序,并给出了详细的解决程序。程序输出最初已通过文献验证。随后,针对广泛的组件温度进行了参数研究。结果表明,考虑到的约束对于可接受的设计和双效吸收式制冷系统的运行控制至关重要。这些模拟将有助于弄清双效吸收式制冷系统在哪些运行条件下有效运行,以及本质上需要哪种控制策略来提高性能系数。根据高压发生器固定温度的运行情况,与在可变高压发生器温度和夹点温度差下工作的同类系统相比,该系统可以将性能系数提高多达31%和84% (高压冷凝器和低压发生器之间分别为5K)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号