The key obstacle in integrating high-voltage direct current (HVDC) point-to-point networks into meshed multiterminal HVDC networks (MTDC) is the absence of dc circuit breakers (DCCBs), which can timely and reliably isolate the faulty HVDC network from the MTDC. In this paper, a novel hybrid-type superconducting DCCB model (SDCCB) is proposed. The SDCCB has a superconducting fault current limiter (SFCL) located in the main line, to limit the fault current until the final trip signal to the SDCCB is given. After the trip signal, insulated-gate bipolar transistor (IGBT) switches located in the main line will commutate the fault current into a parallel line, where dc current is forced to zero by combination of IGBTs and surge arresters. DC fault current behavior in MTDC and fundamental requirements of DCCB for MTDC were described, followed by an explanation of the working principles of the SDCCB. To prove the viability of the SDCCB, a simulation analysis demonstrating SDCCB current interruption performance was done for changing the intensity of dc fault current. It was observed that the passive current limiting by SFCL caused significant reduction in fault current interruption stress for SDCCB. Furthermore, fundamental design requirements for SFCL, including the effect of SFCL quenching impedance on SFCL voltage rating and energy dissipation capacity, were investigated. Finally, advantages and limitations of the SDCCB were highlighted.
机译:将高压直流(HVDC)点对点网络集成到网状多端子HVDC网络(MTDC)中的主要障碍是缺少直流断路器(DCCB),这可以及时可靠地将故障的HVDC网络与电网隔离。 MTDC。本文提出了一种新型的混合型超导DCCB模型(SDCCB)。 SDCCB在干线上有一个超导故障电流限制器(SFCL),用于限制故障电流,直到给出SDCCB的最终跳闸信号为止。在跳闸信号之后,位于主线路中的绝缘栅双极晶体管(IGBT)开关会将故障电流换向并联线路,在该线路中,IGBT和电涌放电器的组合将直流电流强制为零。描述了MTDC中的直流故障电流行为以及MTDC的DCCB的基本要求,然后解释了SDCCB的工作原理。为了证明SDCCB的可行性,进行了仿真分析,演示了SDCCB电流中断性能,用于改变直流故障电流的强度。观察到,SFCL限制的无源电流可显着降低SDCCB的故障电流中断应力。此外,还研究了SFCL的基本设计要求,包括SFCL猝灭阻抗对SFCL额定电压和能量消耗能力的影响。最后,强调了SDCCB的优点和局限性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号