首页> 外文期刊>Applied Energy >Heat transfer studies on a GAXAC (generator-absorber-exchange absorption compression) cooler
【24h】

Heat transfer studies on a GAXAC (generator-absorber-exchange absorption compression) cooler

机译:GAXAC(发电机-吸收器-交换吸收压缩)冷却器的传热研究

获取原文
获取原文并翻译 | 示例
           

摘要

A detailed heat transfer model of GAXAC (generator-absorber-exchange absorption compression) cycle using ammonia-water as working fluid is reported. The effect of UA (heat transfer conductance, kW/K) of each component on COP and cycle capacity is investigated. The results show that UA of the absorber and high temperature generator (HTG) have significant impact on COP and cycle capacity. For a capacity of 11.56 kW, the maximized COP with minimum UA value for all heat exchanging components is found to be 1.185. Further the effect of mass flow rate and inlet temperatures of hot fluid, chilled water and cooling water are also investigated.
机译:报告了使用氨水作为工作流体的GAXAC(发电机-吸收器-交换吸收压缩)循环的详细传热模型。研究了每种成分的UA(传热电导,kW / K)对COP和循环容量的影响。结果表明,吸收器和高温发生器(HTG)的UA对COP和循环容量有重大影响。对于11.56 kW的容量,发现所有热交换组件的最小COP的最大COP为1.185。此外,还研究了质量流量和热流体,冷却水和冷却水入口温度的影响。

著录项

  • 来源
    《Applied Energy》 |2009年第10期|2056-2064|共9页
  • 作者单位

    Department of Mechanical Engineering, Thiagarajar College of Engineering, Madurai 625 015, Tamil Nadu, India;

    Department of Mechanical Engineering, National Institute of Technology, Trichy 620 015, Tamil Nadu, India;

    Institute for Energy Studies, Anna University, Chennai 600 025, Tamil Nadu, India;

  • 收录信息 美国《科学引文索引》(SCI);美国《工程索引》(EI);
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

    ammonia-water; GAX; UA; absorption-compression; heat transfer model;