Measurements have been made of the extent of air exchange between patient rooms in a fully air-conditioned hospital using a tracer-gas method. When the rooms were ventilated at about six air changes per hour, had an excess airflow through the doorway of about 0.1 m.3/sec. and the temperature difference between rooms and corridor was less than 0.5 degrees C., concentrations of the tracer in rooms close to that in which it was being liberated were 1000-fold less than that in the source room. This ratio fell to about 200-fold in the absence of any excess airflow through the doorways. Considerable dilution took place along the corridors so that the concentration fell by around 10-fold for every 10 m. of corridor.
机译:已使用示踪气体法对全空调医院病房之间的空气交换程度进行了测量。当房间每小时换气约六次时,通过门口的过量气流约为0.1 m.3 / sec。并且房间和走廊之间的温度差小于0.5摄氏度,在接近释放它的房间中,示踪剂的浓度比源房间中的示踪剂浓度低1000倍。在没有多余的气流通过门口的情况下,该比率下降到约200倍。沿走廊发生了相当大的稀释,因此浓度每10 m下降约10倍。走廊。