Radiation protection in fixed PET/CT facilities—design and operation

机译:固定PET / CT设施中的辐射防护-设计和运行

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

We describe the design of a fixed positron emission tomography (PET)/CT facility and the use of a simulated instantaneous dose-rate plot to visually highlight areas of potentially high radiation exposure. We also illustrate the practical implementation of basic radiation protection principles based on the use of distance and shielding and the minimisation of time spent in hot areas. Staff whole body doses for 4 years are presented with results of an optimisation study analysing the dose arising from the different phases within each study using direct reading dosemeters. The total whole body dose for all staff for each patient fell from 9.5 μSv in the first full year of operation to 4.8 µSv in 2008. The maximum dose to an individual member of staff per patient decreased over the same period from 3.2 to 0.9 µSv. The optimisation study showed that the highest dose was recorded during the injection phase.
机译:我们描述了固定正电子发射断层扫描(PET)/ CT设施的设计以及模拟瞬时剂量率图的使用,以可视地突出显示潜在的高辐射暴露区域。我们还将说明基于距离和屏蔽的使用以及在炎热地区花费的时间最小化的基本辐射防护原理的实际实施。介绍了4年的全体员工全身剂量,并进行了一项优化研究的结果,该研究使用直读式剂量计分析了每个研究中不同阶段产生的剂量。每位患者所有员工的全身总剂量从手术第一年的9.5 µSv降至2008年的4.8 µSv。同一时间,每位患者单个员工的最大剂量从3.2降至0.9 µSv。优化研究表明,在注射阶段记录了最高剂量。