Heat transfer performance of fresh-air handing device using earth energy

     

摘要

In order to reduce the fresh-air handing energy consumption,a fresh-air handing device using earth energy was presented. The major part is a double pipe soil-air heat exchanger. Its performance was tested in summer and winter. The results show that while the volume of the treated fresh-air is 125 m3/h,in summer,at the outlet of the device,the air temperature is 21.5-24.0 ℃,the air humidity ratio is about 17 g/kg,the greatest temperature drop is about 9 ℃ ,and the largest dehydration quantity is about 6 g/kg. In winter,at the outlet of the device,the air temperature is 15-17 ℃,the air humidity ratio is about 11 g/kg,the largest temperature rise is about 11 ℃,and the largest humidification quantity is about 6 g/kg. Therefore,the application of this new fresh-air handing device can take full advantage of the natural energy,thus effectively reduce the traditional energy consumption for fresh-air handing.