To investigate the partial discharge (PD) online monitoring of transformers by ultra-high-frequency (UHF) approaches,high-qualified UHF antennas are focused on as one key technique. The size of UHF sensor used for PD UHF online monitoring in transformer is excessively large,therefore,it is not convenient for internal installation of transformer. Two types of compact UHF antennas with small sizes,a Hilbert fractal antenna and a small loop antenna are presented. PD experiments of three typically artificial insulation defects are executed and both antennas are used for PD measurement. The spectra of power via frequency of detected PD signals are analyzed and compared. The experimental results show that the Hilbert fractal antenna and small loop antenna are qualified for PD online UHF monitoring.