首页> 中文期刊> 《建筑科学》 >冷库制冷系统液体冷媒除霜结束时的回气管温度研究

冷库制冷系统液体冷媒除霜结束时的回气管温度研究

         

摘要

Hot liquid refrigerant defrosting is a new defrosting method. In this paper, the method of hot liquid refrigerant defrosting was firstly introduced. And then .taking the evaporator muffler temperature as the control parameter that indicated the ending of defrosting, the experimental device and method were described and the experimental data was analyzed. The experimental results demonstrated that taking the muffler temperature as the control parameter that indicated the ending of defrosting in cold storage refrigeration system was feasible. Furthermore, when the temperature in cold storage refrigeration system was higher, the muffler temperature at the end of the defrosting would be lower,and vice versa.%液体冷媒除霜是一种新型的除霜方式.本文首先介绍了液体冷媒除霜的方法,而后对以蒸发器回气管温度作为除霜结束控制参数的实验装置、实验方法和实验数据进行了分析.实验研究结果表明,把回气管温度作为液体冷媒除霜系统除霜结束时的控制参数是可行的,库温高的制冷系统除霜结束时的回气管温度较低,库温低的制冷系统除霜结束时的回气管温度则较高.

著录项

  • 来源
    《建筑科学》 |2013年第2期|74-77|共4页
  • 作者单位

    天津商业大学冷冻冷藏技术教育部工程研究中心天津市制冷技术重点实验室天津市制冷技术工程中心,天津300134;

    天津商业大学冷冻冷藏技术教育部工程研究中心天津市制冷技术重点实验室天津市制冷技术工程中心,天津300134;

    天津商业大学冷冻冷藏技术教育部工程研究中心天津市制冷技术重点实验室天津市制冷技术工程中心,天津300134;

    河南中烟工业有限责任公司,郑州450000;

  • 原文格式 PDF
  • 正文语种 chi
  • 中图分类 制冷技术;
  • 关键词

    液体冷媒除霜; 回气管温度; 控制参数;