首页> 外文学位 >Potentials for COP increase in vapor compression systems.
【24h】

Potentials for COP increase in vapor compression systems.

机译:蒸气压缩系统中COP的潜力会增加。

获取原文
获取原文并翻译 | 示例

摘要

This work presents an experimental and numerical study of three different opportunities for COP increase in vapor compression systems: work recovery ejectors, condenser subcooling and increase of relative size of heat exchangers (HXs).;Regarding work recovery ejectors, experimental results showed that the COP of the ejector system increased between 8.2% and 14.8% when compared to a conventional expansion valve system operating with R410A. The two major mechanisms of improvement of the ejector system were quantified separately: COP gains between 1.9% to 8.4% were solely due to the work recovery, while liquid-feeding the evaporator alone was responsible for 4.9% to 9.0% of COP gain. Overall ejector efficiencies from 12.2% to 19.2% were achieved.;A major portion of this dissertation explores the effects of condenser subcooling on the COP of vapor compressions systems. It is shown that, as condenser subcooling increases, the COP reaches a maximum as a result of a trade-off between increasing refrigerating effect and specific compression work. A thermodynamic analysis pointed out that refrigerants with large ratio of liquid specific heat to latent heat of vaporization tend to benefit more from condenser subcooling. Numerical results suggested that R1234yf systems would benefit the most from condenser subcooling in comparison to R410A, R134a, and R717. Experimental results obtained with a vehicular air conditioning system revealed COP gains between 6% and 44% for R1234yf and 2% to 21% for R134a due to condenser subcooling. Results also indicated that the larger the air-refrigerant temperature difference in the condenser, the higher the COP maximizing subcooling and the COP gains from condenser subcooling. Additional experiments showed that the presence of an internal heat exchanger reduces the benefits of the condenser subcooling. With a unique set of microchannel condensers, an experimental comparison between subcooling generated in non-designated area (NDA) and designated area (DA) of the condenser showed that both configurations yielded similar values of maximum COP improvement within the operating conditions considered. It was also demonstrated that condensers with a higher air-refrigerant temperature difference would require a larger COP maximizing area ratio allocated for subcooling. Nevertheless, a fixed designated area yielded near maximum COPs within a reasonable range of operating conditions. The effect of refrigerant mal-distribution on the performance of a two-pass parallel-flow microchannel condenser as well as on the overall system COP is numerically investigated. The results showed a COP deterioration of not more than 3% for the worst case of mal-distribution considered.;The effect of the size of the heat exchangers (HXs) relative to the cooling capacity on the performance of actual residential air conditioning systems has been experimentally and numerically investigated for R410A and transcritical R744. Experiments were carried out in a limited range of operating conditions but an experimentally validated model was used to extrapolate trends. As the relative size of the HXs was increased, a maximum COP of 9.5 (without fans power) was experimentally measured with R410A, a value much higher than off-the-shelf units but that is only 28% of the ideal Evans-Perkins COP. Lower compressor isentropic efficiency, condenser subcooling and evaporator superheat were pointed out as constraints for further COP improvement by oversizing the HXs. These constraints were removed in the numerical model and results showed that further oversizing HXs can improve COP but sensitivity is reduced significantly as HXs become larger relative to the cooling capacity. Experimental and numerical results indicated that the COP of an air conditioning system operating with transcritical R744 is less sensitive to the relative size of the HXs than that of the same system operating with R410A. Transcritical R744 becomes more competitive in terms of COP as the size of HXs is reduced while R410A by far outperforms transcritical R744 in a larger system. In addition, it is suggested that the COP ratio to the theoretical limit of Evan-Perkins cycle could be used as a measure of the heat exchangers relative size.
机译:这项工作提供了对蒸气压缩系统中COP增加的三种不同机会的实验和数值研究:功回收喷射器,冷凝器过冷和热交换器相对尺寸的增加。;关于功回收喷射器,实验结果表明COP与使用R410A运转的传统膨胀阀系统相比,喷射器系统的总升幅在8.2%至14.8%之间。改善喷射器系统的两个主要机制分别进行了量化:COP增益在1.9%至8.4%之间仅是由于工作恢复,而液体进给蒸发器仅占COP增益的4.9%至9.0%。整体喷射效率达到了12.2%至19.2%。;本文的主要部分探讨了冷凝器过冷对蒸气压缩系统COP的影响。结果表明,随着冷凝器过冷度的增加,由于制冷效果的提高与特定压缩功之间的权衡,COP达到最大值。热力学分析指出,液体比热与汽化潜热之比大的制冷剂往往会受益于冷凝器过冷。数值结果表明,与R410A,R134a和R717相比,R1234yf系统将受益于冷凝器过冷。用车载空调系统获得的实验结果表明,由于冷凝器过冷,R1234yf的COP增益在6%至44%之间,R134a的COP增益在2%至21%之间。结果还表明,冷凝器中的空气制冷剂温度差越大,COP使过冷度最大化和从冷凝器过冷度获得的COP越高。其他实验表明,内部热交换器的存在降低了冷凝器过冷的好处。使用一组独特的微通道冷凝器,在冷凝器的非指定区域(NDA)和指定区域(DA)中产生的过冷之间的实验比较表明,在所考虑的运行条件下,两种配置均可产生相似的最大COP改善值。还证明了具有较高的空气制冷剂温度差的冷凝器将需要更大的COP最大化分配给过冷的面积比。但是,在合理的操作条件范围内,固定的指定区域产生的COP接近最大。数值研究了制冷剂分布不均对两程平行流微通道冷凝器性能以及整个系统COP的影响。结果表明,在考虑到分布最差的最坏情况下,COP劣化不超过3%.;热交换器(HXs)的尺寸相对于制冷量的影响对实际的家用空调系统的性能具有对R410A和跨临界R744进行了实验和数值研究。在有限的操作条件范围内进行了实验,但是使用了经过实验验证的模型来推断趋势。随着HX相对尺寸的增加,使用R410A实验测得的最大COP(无风扇功率)为9.5(该值比现有设备高得多),但仅为理想Evans-Perkins COP的28% 。指出降低压缩机的等熵效率,冷凝器过冷和蒸发器过热是限制HX尺寸进一步改善COP的制约因素。在数值模型中消除了这些限制,结果表明,进一步加大尺寸的HX可以提高COP,但随着HX相对于冷却能力的增大,灵敏度会大大降低。实验和数值结果表明,与使用R410A运行的同一系统相比,使用跨临界R744运行的空调系统的COP对HX的相对大小更不敏感。随着HX尺寸的减小,跨临界R744在COP方面更具竞争力,而在大型系统中,R410A的性能远远超过跨临界R744。此外,建议将COP比值与Evan-Perkins循环的理论极限值一起用作换热器相对尺寸的度量。

著录项

  • 作者

    Pottker, Gustavo.;

  • 作者单位

    University of Illinois at Urbana-Champaign.;

  • 授予单位 University of Illinois at Urbana-Champaign.;
  • 学科 Mechanical engineering.
  • 学位 Ph.D.
  • 年度 2012
  • 页码 274 p.
  • 总页数 274
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类
  • 关键词

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号