Back in 2008 IBM reintroduced water cooling technology into its high performance computing platform, the Power 575 Supercomputing node/system. Water cooled cold plates were used to cool the processor modules which represented about half of the total system (rack) heat load. An air-to-liquid heat exchanger was also mounted in the rear door of the rack to remove a significant fraction of the other half of the rack heat load; the heat load to air. Water cooling enabled a compute node with 34% greater performance (Flops), resulted in a processor temperature 20–30 °C lower than that typically provided with air cooling, and reduced the power consumed in the data center to transfer the IT heat to the outside ambient by as much as 45%.
机译:早在2008年,IBM将水冷技术重新引入其高性能计算平台Power 575超级计算节点/系统。水冷式冷却板用于冷却处理器模块,该模块约占系统(机架)总热负荷的一半。空气-液体热交换器也安装在机架的后门中,以消除机架热负荷的另一半的很大一部分。空气的热负荷。水冷却使计算节点的性能(触发器)提高了34%,使处理器温度比通常使用风冷提供的温度低20–30°C,并减少了数据中心将IT热量传递到计算机的能耗。外部环境多达45%。