Reducing arc flash risk with the application of protective relays

机译:通过使用保护继电器降低电弧闪光的风险

获取原文

摘要

The exposure to an arc flash high incident energy fault to technicians operating low and medium voltage switching equipment is a daily hazard in the workplace and there is an opportunity to improve safety. While PPE protects for first and second degrees burns it could not provide sufficient protection for the impact and forces that a high incident energy arcing fault produces and the gases released for exposures over 40 cal/cm2. One solution is to reduce the incident energy of the arcing fault below 40 cal/cm2, This paper analyzes methods to reduce the exposure of personnel to high-energy arcing faults to levels below 40 cal/cm2, and also defines a method to determine the limits of coordination among protective devices to identify where the selectivity could be jeopardized.
机译:操作低压和中压开关设备的技术人员会遇到电弧高入射能量故障,这是工作场所中的日常危险,并且有机会提高安全性。虽然PPE可以防止一度和二度烧伤,但它不能为高入射能量电弧故障产生的冲击和力以及暴露于40 cal / cm 2 所释放的气体提供足够的保护。一种解决方案是将电弧故障的入射能量降低到低于40 cal / cm 2 ,本文分析了将人员在高能电弧故障中的暴露降低到40 cal / cm < sup> 2 ,还定义了一种方法来确定保护设备之间的协调极限,以识别选择性可能受到损害的地方。