首页> 外文会议>IEEE Workshop on Power Electronics and Power Quality Applications >Influence of Grid-Tied PV Systems and EV Charging Stations on Power Transformers Failure Rate Behaviour
【24h】

Influence of Grid-Tied PV Systems and EV Charging Stations on Power Transformers Failure Rate Behaviour

机译:网格绑定PV系统的影响和EV充电站对电力变压器故障率行为的影响

获取原文

摘要

This document presents the analysis of the failure rate of an oil-inmmersed header distribution transformer due to the presence of current harmonics produced by a Grid-Tied PV system and slow charging stations. Monte-Carlo simulations were performed to generate harmonic profiles in order to calculate the accelerated aging factor that along with the transformer health index determine the behavior of the transformer’s failure rate. The results show that harmonic distortion does not have a significant influence on the transformer life reduction, and that degradation of solid and liquid insulation is one of the cause of increase in the failure rate in long-term as they have a high relative weight in the health index.
机译:由于存在电网连接的光伏系统和慢充电站,本文件由于存在电流谐波,本文件提出了对燃油移位分配变压器的故障率的分析。进行Monte-Carlo模拟以产生谐波型材,以便计算加速的老化因子以及变压器健康指数的加速老化因子决定了变压器故障率的行为。结果表明,谐波畸变对变压器寿命的降低没有显着影响,并且固体和液体绝缘的降解是长期失效率增加的原因之一,因为它们具有高相对重量健康指数。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有