首页> 外文会议>IEEE Asia Power and Energy Engineering Conference >Analysis of Single-phase Short-circuit Current Suppression Measures at Converter Stations and Their Effects on Power System Reliability
【24h】

Analysis of Single-phase Short-circuit Current Suppression Measures at Converter Stations and Their Effects on Power System Reliability

机译:转换器站单相短路电流抑制措施分析及其对电力系统可靠性的影响

获取原文

摘要

Aiming at the issue that the single-phase short-circuit current at the 500kV side of Yibin and Fulong converter stations has exceeded the breaking capacity of breaker, the reason is analyzed and the measures are put forward to reduce the single-phase short circuit, including limiting the output of thermal power near field, converter transformers neutral grounding by small reactance and 500kV lines adding series reactors. The limiting effects of single-phase short-circuit current and the impacts on power grid equipment operation and power supply reliability of different measures are compared. Feasible suggestions for reducing single-phase short-circuit current and improving power grid reliability are given.
机译:针对宜宾和富隆转换器站500kV侧的单相短路电流已经超过断路器的断裂能力,分析了原因,提出了措施,以减少单相短路,包括限制近场的热功率输出,转换器变压器通过小型电抗和500kV线加入串联反应堆。比较单相短路电流的限制效果及对电网设备运行和电源可靠性的影响不同措施。给出了减少单相短路电流和提高电网可靠性的可行建议。