首页> 外文会议>Asia-Pacific International Conference on Lightning >Lightning fault analysis of 10 kV hybrid distribution lines
【24h】

Lightning fault analysis of 10 kV hybrid distribution lines

机译:10 kV混合分布线的雷电故障分析

获取原文

摘要

Hybrid structure with electric cables and overhead lines are widely used in the 10 kV urban distribution network. In this paper, simulating conditions of the hybrid network are analyzed as an example, a fault simulation test platform combined of bare conductor, insulated conductor and insulators are established, the failure and the influencing factors are analyzed. The results show that: (1) the insulation damage of insulated conductors is the main reason of the line broken; (2) insulation damage will cause the vicious cycle of equipment insulation, which will causes the insulation damage of cable accessories, and then lead to the fault of the hybrid 10 kV distribution network. Aiming at the fault risk of the hybrid 10 kV distribution network, this paper puts forward some applicable countermeasures. The related research results can provide technical reference for the operation and maintenance of the hybrid 10 kV distribution network.
机译:具有电缆和架空线的混合结构广泛用于10 kV城市配送网络。在本文中,分析了混合动力网络的模拟条件作为示例,建立了裸导体,绝缘导体和绝缘体的故障仿真测试平台,故障和影响因子进行了分析。结果表明:(1)绝缘导体的绝缘损伤是断线的主要原因; (2)绝缘损坏将导致设备绝缘的恶性循环,这将导致电缆配件的绝缘损坏,然后导致混合10 kV分配网络的故障。旨在涵盖混合动力10 kV配电网络的故障风险,本文提出了一些适用的对策。相关的研究结果可以为混合动力10 kV分配网络的操作和维护提供技术参考。