Hybrid structure with electric cables and overhead lines are widely used in the 10 kV urban distribution network. In this paper, simulating conditions of the hybrid network are analyzed as an example, a fault simulation test platform combined of bare conductor, insulated conductor and insulators are established, the failure and the influencing factors are analyzed. The results show that: (1) the insulation damage of insulated conductors is the main reason of the line broken; (2) insulation damage will cause the vicious cycle of equipment insulation, which will causes the insulation damage of cable accessories, and then lead to the fault of the hybrid 10 kV distribution network. Aiming at the fault risk of the hybrid 10 kV distribution network, this paper puts forward some applicable countermeasures. The related research results can provide technical reference for the operation and maintenance of the hybrid 10 kV distribution network.
机译:带有电缆和架空线的混合结构被广泛用于10 kV城市配电网络中。以混合网络的仿真条件为例,建立了裸导体,绝缘导体和绝缘子相结合的故障仿真测试平台,分析了故障和影响因素。结果表明:(1)绝缘导体的绝缘破坏是断线的主要原因; (2)绝缘破坏会引起设备绝缘的恶性循环,从而会导致电缆附件的绝缘破坏,进而导致10 kV混合配电网故障。针对10 kV混合配电网的故障风险,提出了一些适用的对策。相关研究成果可为10 kV混合配电网的运行和维护提供技术参考。