首页> 外文会议>International Conference on Industrial Engineering, Applications and Manufacturing >Research of Single-Phase Faults in 6-35 KV Branched Overhead Distribution Network
【24h】

Research of Single-Phase Faults in 6-35 KV Branched Overhead Distribution Network

机译:6-35 kV分支架空配电网单相故障研究

获取原文

摘要

The relevance of the problem discussed in the paper is stipulated by the risk of electric shock for people and animals near 6-35 kV overhead lines. It is necessary to find the short circuit location in distribution networks in the shortest possible time. Inspection of extensive, branched and hard-to-reach overhead sections takes a lot of time, so it is easier and quicker to use special portable devices for search of ground fault location. As operating experience shows, search devices produced in Russia fail to determine location of "non-metallic" single-phase damage. The aim of this study is to identify the causes for failures of existing portable devices and to develop new ways of searching short circuit location. For this purpose, operation of 6-35 kV distribution network at different single-phase faults is analyzed. An equivalent circuit of the studied distribution network has been developed during the analysis. The authors have also completed a series of calculations of tension and currents of different harmonic components in network branches at different types of single-phase damages. They have studied the influence of resistance change in the place of short circuit on harmonic tension and current components and estimated emission of electromagnetic field under real overhead wires of the studied network at artificial single-phase damages. Cumulative amplitude-phase analysis of the highest harmonic current and tension components enables development of a new way of searching for ground fault location in the extensive 6-35 kV overhead distribution network. The main reason of failure of portable searching devices appears to be a level in-time variation of the highest harmonic current components.
机译:本文讨论的问题的相关性由触电靠近6-35 kV架空线的人和动物的风险规定。有必要在最短的时间内找到分发网络中的短路位置。检查广泛,分支和难以达到的架空部分需要大量的时间,因此使用特殊便携式设备更容易且更快地搜索接地故障位置。作为操作经验表明,俄罗斯生产的搜索设备未能确定“非金属”单相损坏的位置。本研究的目的是识别现有便携式设备的故障的原因,并开发新的搜索短路位置的方式。为此目的,分析了不同单相故障处的6-35 kV分配网络的操作。在分析期间已经开发了研究的分配网络的等效电路。作者还在不同类型的单相损坏的网络分支中完成了一系列的张力和不同谐波分量的电流。他们已经研究了在人造单相损伤的研究网络中实际架空线上的谐波张力和电流分量的谐波张力和电流元件的估计发射的影响。最高谐波电流和张力组件的累积幅度分析能够开发在广泛的6-35 kV架空配电网中寻找接地故障位置的新方法。便携式搜索设备失败的主要原因似乎是最高谐波电流分量的水平时间变化。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号