首页> 外文会议>IEEE International Conference on Adaptive Science and Technology >Multimachine transient stability analysis of the expanded 49 bus, 330KV Nigeria power system
【24h】

Multimachine transient stability analysis of the expanded 49 bus, 330KV Nigeria power system

机译:330kV尼日利亚电力系统扩展49总线的多机速暂态稳定性分析

获取原文

摘要

The recent power sector reform in Nigeria has thrown up enormous challenges in this sector, ranging from the construction of more power stations, new transmission lines and substations. The existing network of 8-plants and 26 bus-bars expanded to a network of 16 generating plants with 49 bus-bars. Power flow evaluation of this expanded 330KV network was done using the Newton-Raphson technique, while transient stability analysis of the power system was simulated by direct method using ode45 MATLAB programmed functions. The results show better network configuration, though buses interconnected via long transmissions lines recorded high voltage profile violation. The critical clearing times and stability margins for three-phase faults at buses 3 (line 3–44) and 31 (line 2–31) were established as 0.21 second, 0.238 and 0.29 second, 0.448 respectively. The result provided a suite of specifications and standards for the expanded grid system.
机译:最近尼日利亚的电力部门改革在这一部门突出了巨大的挑战,从建造更多的发电站,新的传输线和变电站。现有的8厂网络和26个汇流条扩展到16个具有49个母线的16个发电厂的网络。使用Newton-Raphson技术进行了这种扩展的330kV网络的功率流量评估,而使用ODE45 MATLAB编程功能的直接方法模拟了电力系统的瞬态稳定性分析。结果显示了更好的网络配置,虽然通过长传输线互连的总线记录了高压分布违规。公共汽车3(3-44)和31(第2-31线)和31(第2-31线)的三相故障的关键清算时间和稳定性边缘分别建立为0.21秒,0.238和0.29秒,0.448。结果为扩展网格系统提供了一套规格和标准。