首页> 外文期刊>International Journal of Applied Engineering Research >Transient Stability Assessment of the Existing 8 Machines, 26 Bus, 330KV Nigeria Power System via Direct Method
【24h】

Transient Stability Assessment of the Existing 8 Machines, 26 Bus, 330KV Nigeria Power System via Direct Method

机译:通过直接方法评估现有8台机器,26总线,330KV尼日利亚电力系统的暂态稳定性

获取原文
获取原文并翻译 | 示例
           

摘要

This paper assesses the transient stability of the existing Nigeria power system comprising 8-plants and 26 bus-bars through direct method. It deployed multimachine technique in the stability analysis. The result of power flow evaluation performed by Newton-Raphson technique indicated no voltage profile violations, while losses in lines 10-9, 10-8, 9-7, and 13-16 were above 10MW each. The transient stability analysis simulation by ode45 MATLAB programmed functions for a three-phase fault at bus 16, line 13-16 led to the establishment of the critical clearing time of 0.21 second and the stability margin of 0.238.
机译:本文通过直接方法评估了由8个工厂和26个母线组成的尼日利亚现有电力系统的暂态稳定性。在稳定性分析中采用了多机技术。通过牛顿-拉夫森(Newton-Raphson)技术进行的潮流评估结果表明,没有违反电压曲线,而10-9、10-8、9-7和13-16线的损耗均高于10MW。通过ode45 MATLAB编程的功能对总线16、13-16线处的三相故障进行的暂态稳定性分析仿真,确定了0.21秒的临界清除时间和0.238的稳定裕度。