This paper describes the design of earthing conductor, electrode positioning of unsymmetrical earthing system for an elevated metro station. The technique depends upon determination of electric field intensity around the earthing system and distribution of current injected into the soil. The electric field intensity is determined by charge simulation method. Two layer soil model is adopted as per IEEE 80:2000 standard for the analysis. The procedure provides accurate voltage profile for determining touch and step potential. It is found that unsymmetrical earth grid is superior over symmetrical earth grid. Simulation study is done on MATLAB/Simulink R2014b and ETAP 6.0. The obtained result is verified by comparing the analytically obtained data with numerical method. The theoretical findings can be useful for practical implementation in any metro station.
机译:本文介绍了升高地铁站的接地导体的设计,不对称接地系统的电极定位。该技术取决于确定围绕接地系统的电场强度和喷射到土壤中的电流分布。电场强度由电荷仿真方法确定。根据IEEE 80:2000标准采用两层土壤模型。该过程提供精确的电压型材,用于确定触摸和步长电位。发现不对称地球网格在对称地球网上优越。模拟研究是在MATLAB / SIMULINK R2014B和ETAP 6.0上进行的。通过使用数值方法比较分析获得的数据来验证所获得的结果。理论上的发现对于任何地铁站的实际实施都很有用。