首页> 外文会议>International Institute of Refrigeration;Institut International Du Froid;IIR International Conference on HFO Refrigerants and Blends >Falling film evaporation and pool boiling of HFO1233zd(E) on a low finned tube with thermal spray coating
【24h】

Falling film evaporation and pool boiling of HFO1233zd(E) on a low finned tube with thermal spray coating

机译:热喷涂低翅片管上HFO1233zd(E)的降膜蒸发和池沸腾

获取原文

摘要

A falling film evaporator is attracting attention to reduce the refrigerant filling amount. For heat transferenhancement of the falling film evaporation, forming and keeping a thin liquid film on the heat transfer surfaceare important. In this study, thermal spray coating was applied on a low finned tube. The contribution ofnucleate boiling in the film evaporation heat transfer of HFO1233zd(E) was evaluated from the comparison inthe experimental results of pool boiling using the same test section. The tube length was 50 mm and thediameter at the top of the fins was 19.05 mm. The liquid film flow rate was fixed at 0.033 kg×m~(–1)×s~(–1) and theheat flux was varied from 10 to 85 kW×m~(-2). As a result, it was shown that the enhancement factor by thecoating was up to 2.0 for falling film evaporation and was higher than the pool boiling.
机译:降膜蒸发器正在引起人们的注意,以减少制冷剂加注量。用于传热

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信