Applicability of Stockwell transform in diagnosing impulse faults of a transformer

机译:股票交易到诊断变压器脉冲故障的适用性

获取原文

摘要

Lightning impulse test is one of the mandatory tests that every transformer has to undergo after assembly. This is done for assessing the condition of insulation of its windings. In the case of any fault, the neutral current and/or tank current contain(s) typical signatures depending on the nature and location of the fault. Since these current signals are non-stationary in nature hence each of these faults can be classified from such a transformation technique that has the time-frequency localization property. This paper investigates the performance of Stockwell Transform, popularly known as S-transform, for identification of insulation failures of a transformer winding during impulse test. The present study is restricted only to identify failure of winding insulation due to some defects that are already present in the winding and have not been developed due to the application or during the propagation of impulse voltage applied during the test. The results presented in this paper are for simulated models of a 3 MVA and a 5 MVA transformer. From the results, the prospect of S-transform in identifying the nature and the location of winding faults in distribution transformers is reflected.
机译:闪电脉冲测试是每个变压器在装配后必须进行的强制性测试之一。这是为了评估其绕组绝缘的条件。在任何故障的情况下,取决于故障的性质和位置,中性电流和/或罐电流包含典型的签名。由于这些电流信号在自然界中是非静止的,因此这些故障中的每一个可以从具有时频本地化属性的这种变换技术分类。本文调查了股票交易的性能,普遍称为S变换,用于识别脉冲试验期间变压器绕组的绝缘故障。本研究仅限于识别由于已经在绕组中存在的一些缺陷而识别绕组绝缘的失效,并且尚未由于应用或在测试期间施加的脉冲电压的传播期间开发。本文提出的结果用于3 MVA和5 MVA变压器的模拟模型。从结果中,反映了识别分布变压器中绕组故障的性质和绕组故障的性质的前景。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号