THE EFFECT OF THE NETWORK VOLTAGE AHD CURRENT ON THE EROSION OF SWITCHING CONTACTS

机译:网络电压和电流对开关触点腐蚀的影响

获取原文

摘要

Investigations show that the erosion is determined by the current flowing through the arc, so the form of the current must be analysed as well. Because of the deformation of the sinusoidal current form is caused by the electric arc the ratio of the arc voltage and the network voltage has an important role. The relation between the current - time integral, namely the arc energy and the erosion is presented here at currents 10-100 A and voltages 63-220 V. In alternating current circuits the switching out may occur in any phase position, so in the computer calculations every case of separation-instant is taken consideration and an average of energy and charge is calculated. At rated voltage the erosion of the switching in carried out with multiple values of the rated current is considered too at the determination of the total erosion.
机译:研究表明,侵蚀由流过弧的电流确定,因此也必须分析电流的形式。 由于正弦电流形式的变形是由电弧引起的电弧电压和网络电压的比率具有重要作用。 当前 - 时间积分,即电弧能量和侵蚀之间的关系在此处在电流10-100a和电压63-220v中呈现。在交流电路中,切换可能在任何相位位置,所以在计算机中发生 计算每个分离瞬间的计算是考虑的,并且计算能量和电荷平均值。 在额定电压下,在总侵蚀的测定中也考虑了具有多个额定电流的多个值的开关的腐蚀。