摘要

In this paper, the problem of online change-point detection of voltage imbalance in a three-phase power system using phasor measurement unit (PMU) data is considered within a sequential hypothesis-testing framework. A general model for the positive-sequence data from a PMU measurement at the time domain and off-nominal frequencies is presented. The new formulation, which assumes an additional Gaussian noise, enables fast online detection of imbalance. Closed-form expressions of the cumulative sum (CUSUM) and generalized likelihood ratio (GLR) tests are developed for detection of imbalances. The performance of the change-point detection procedures is evaluated using the average-run-length and the expected detection delay. Numerical simulations show that the proposed method can be used for enhanced situational awareness in future grid management systems and demonstrate the ability to inform strategies for advancing grid capabilities by using change-point detection methods.
机译:在本文中,在顺序假设测试框架内考虑了使用量相测量单元(PMU)数据的三相电力系统中电压不平衡的在线改变点检测问题。呈现了来自时域和非标称频率的PMU测量的正序数据的一般模型。具有额外高斯噪声的新配方,可以快速在线检测不平衡。开发了累积和累积总和(CUSUM)和广义似然比(GLR)测试的闭合表达,用于检测不平衡。使用平均流量长度和预期的检测延迟来评估变更点检测程序的性能。数值模拟表明,该方法可用于增强未来电网管理系统的情境感知,并展示通过使用变更点检测方法为推进网格能力的策略提供信息的能力。