首页> 外文会议>IEEE Power and Energy Society Innovative Smart Grid Technologies Conference >PMU-based online change-point detection of imbalance in three-phase power systems
【24h】

PMU-based online change-point detection of imbalance in three-phase power systems

机译:基于PMU的三相电力系统不平衡在线变化点检测

获取原文

摘要

In this paper, the problem of online change-point detection of voltage imbalance in a three-phase power system using phasor measurement unit (PMU) data is considered within a sequential hypothesis-testing framework. A general model for the positive-sequence data from a PMU measurement at the time domain and off-nominal frequencies is presented. The new formulation, which assumes an additional Gaussian noise, enables fast online detection of imbalance. Closed-form expressions of the cumulative sum (CUSUM) and generalized likelihood ratio (GLR) tests are developed for detection of imbalances. The performance of the change-point detection procedures is evaluated using the average-run-length and the expected detection delay. Numerical simulations show that the proposed method can be used for enhanced situational awareness in future grid management systems and demonstrate the ability to inform strategies for advancing grid capabilities by using change-point detection methods.
机译:本文在相继的假设检验框架内考虑了使用相量测量单元(PMU)数据在线检测三相电力系统中电压不平衡的问题。提出了在时域和非标称频率下从PMU测量获得的正序数据的通用模型。新的公式假设了额外的高斯噪声,可以快速在线检测不平衡。累积和(CUSUM)和广义似然比(GLR)检验的闭式表达式被开发用于检测失衡。使用平均行程长度和预期的检测延迟来评估更改点检测过程的性能。数值模拟表明,所提出的方法可用于增强未来电网管理系统中的态势感知,并展示了通过使用变更点检测方法来告知提高电网能力的策略的能力。