首页> 外文会议>International Conference on System Reliability and Science >Influence investigation from the forced draught fan mode on the characteristics of an air-cooled power plant
【24h】

Influence investigation from the forced draught fan mode on the characteristics of an air-cooled power plant

机译:从强制粉丝模式对风冷发电厂特性的影响

获取原文

摘要

In view of the critical suction effect of the forced draught fans in the air-cooled steam condenser (ACSC), it is momentous to investigate and optimize the fan mode to acquire a better synthetical performance of the power plant. A verified numerical model of a 2×600MW power plant [1] is specified to discuss the influence from the different rotating speed regulation schemes on the performance of the air-cooled power plant at the design wind angle of β=22.5°. It is found that as a result of the rotating speed regulation of the forced draught fans, the improvement for the performance of the air-cooled power plant arise. It is concluded that the rotating speed regulation for the whole fan array should be proposed because the maximum net power elevation compared to the design case is applicable at all the appointed wind speeds for the fan array case.
机译:鉴于强制蒸汽冷凝器(ACSC)中强制牵引式风扇的临界吸入作用,旨在调查和优化风扇模式,以获得电厂的更好的综合性能。指定了2×600MW发电厂[1]的经过验证的数值模型,以讨论不同旋转速度调节方案对β= 22.5°的设计风角在风冷发电厂的性能的影响。结果发现,由于强制草案风扇的旋转速度调节,出现了风冷发电厂性能的改进。得出结论是,应提出整个风扇阵列的旋转速度调节,因为与设计外壳相比的最大净功率高度适用于风扇阵列情况的所有指定的风速。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有