A Study on the Cool Charge Characteristics of Ice Storage Plate Filled with Eutectic salt

机译:用共晶盐的冰储存板冷藏特性研究

获取原文

摘要

The electricity load imbalance between day and night of air conditioning greatly affect the power generation cost and safe operation of power grid. Because of the important role in balance the peak and night electricity load, the Cool storage technology more and more attention at home and abroad. A cool storage experimental apparatus with internal melt ice-on-coil was set up, and on which the heat-transfer characteristics have been determined. The experimental results show that: The inlet temperature of refrigerant, when entering the ice storage tank, has an larger influence on the process of cool storage than the flow amount of the cooling medium. It is found by analyzing the process of experiment about storage that the suitable outlet temperature of the cooling medium is 1C while the flow amount of the cooling medium is 0.274 m~3/h. The research results can provide help for the energy-saving design of air conditioning.
机译:空调白天和夜间之间的电力负荷不平衡大大影响电网的发电成本和安全操作。由于平衡峰值和夜电负荷的重要作用,酷蓄能技术越来越受到国内外的关注。建立了具有内部熔体型卷线圈的冷却储存实验装置,并确定了传热特性。实验结果表明:制冷剂的入口温度在进入冰储罐时对冷却介质的流量的冷却过程具有更大的影响。通过分析关于储存的实验过程,即冷却介质的合适出口温度为1℃,而冷却介质的流量为0.274m〜3 / h。研究结果可以为空调节能设计提供帮助。